PRODUCT CENTER Three Position Mechanism
CJ8三工位机构
CJ8三工位机构
CJ8三工位机构
CJ8 Three Position Mechanism
CJ8 operating mechanism can be used for closing and breaking ZF23-126, ZF -126 and isolation switches, grounding switches and load switches with the required torque equivalent. It is a dual-motor type three-station mechanism.
This mechanism is a three-station mechanism, and one mechanism can operate an isolation switch and a grounding switch to realize the function of closing and opening of the isolation switch. The mechanism has two operation modes at the same time: manual and electric.
This mechanism is a dual-motor double-screw nut transmission structure, symmetrical left and right, and a motor and a set of screw nuts correspond to operate a set of switches.
Technical Parameters

1. The output angle of this mechanism is ±195° (can be customized according to user requirements).

2. Output torque: 120N.m.

3. The rated voltage dividing and closing time ≤2S.

4. Use CSK type magnetic blow switch. The current that can be continuously passed through the contact is 10A at AC220V and 3A at DC220V.

5. Use the F10 type auxiliary switch. Normally, it is two 10 open and 10 closed auxiliary switches.

6. The secondary connector is an imported industrial connector, the protection level can reach IP68 level, and one mechanism is conventionally equipped with two 46-core industrial connectors. There are several types of secondary industrial connectors, such as 24-pin, 32-pin, and 46-pin.

7. Technical parameters of energy storage motor.


Model

HDZ-23610C

Rated operating voltage

AC and DC 220V

Rated output power of the motor

360W

Normal operating voltage range

85%-110%

Diagram

Engineering Drawings

Xi'an Xidian Shashi Mao 110kV substation station CJ8 mechanism


Ordering instructions
1. Control voltage and motor voltage;
2. an output angle;
3. Installation size;
4. Outdoor or indoor use;
5. The output mode of the output shaft; 6. The starting position (angle) of the output shaft when the opening position is opened; 7. The logarithm of the auxiliary contact of the auxiliary switch;