PRODUCT CENTER Three Position Mechanism
CJ23-550型三工位操动机构
CJ23-550 Three-station operating mechanism
CJ23-550 operating mechanism can be used for the required torque of Pinggao ZF27-550 and the closing and breaking of the equivalent isolation switch, grounding switch and load switch.
This mechanism is a three-station mechanism, and one mechanism can operate an isolation switch and a grounding switch, so as to realize the functions of closing and opening of the isolation switch and closing and opening of the grounding switch. The mechanism has two operation modes at the same time: manual and electric.
The first 550kV three-phase linkage three-station mechanism in China
Technical Parameters

1. The output angle of this mechanism is DS=382°ES=382° (can be customized according to user requirements).

2. Output torque: 120N·m.

3. The rated voltage closing and opening time <2s.

4. Technical parameters of energy storage motor

    Model

DS is HDZ-215005C type

ES is HDZ-215005C

Rated operating voltage

≈220V

≈220V

Rated output power of the motor

DS=1500W

DS=1500W

Normal operating voltage range

85%-110%

85%-110%

5. With the CSK type magnetic blow switch, the current that can be continuously passed through the contact is 10A at AC220V and 3A at DC220V.

6. Use the F10 type auxiliary switch. F10 auxiliary switch. Normally, it is 10 open and 10 closed, and it can reach up to 20 open and 20 closed. The continuous current that can be passed through the contact is 10A at AC220 and 5A at DC220.

7. The secondary connector is an imported industrial connector, and the protection level of the outdoor mechanism can reach IP68 level, and a mechanism can also be equipped with two or three industrial connectors with a 46-core industrial connector. There are several types of secondary industrial connectors, such as 24-pin, 32-pin, and 46-pin.

 
Diagram

Engineering Drawings

Ordering instructions
1. Control voltage and motor voltage;
2. an output angle;
3. Installation size;
4. Outdoor or indoor use;
5. The output mode of the output shaft; 6. The starting position (angle) of the output shaft when the opening position is opened; 7. The logarithm of the auxiliary contact of the auxiliary switch;