PRODUCT CENTER Three Position Mechanism
HYT5A型 电动弹簧操动机构
HYT5A Electric Spring Actuator
HYT5A spring operating mechanism can be used for all kinds of 126KV common box GIS, which is used for the opening and closing of fast grounding switch or fast isolation switch, or isolation switch, grounding switch and load switch with the required torque comparable. The miniaturized design of the mechanism and the thin thickness make it very suitable
GIS quick grounding switch. This mechanism uses the principle of spring symmetry and centering, and through the forward and reverse rotation function of the motor, the mechanism can compress the spring to achieve rapid opening and closing. The mechanism has two operation functions at the same time: manual and electric.
Technical Parameters

1. The output angle of this mechanism is 60°+1° (can be customized according to user requirements, but the angle cannot exceed 90 degrees).

2. The spring output closing (opening) power is 169~244J.

3. The combined time of the institution <6s

4. Technical parameters of energy storage motor

    Model

HDZ-23603C type

Rated operating voltage

≈220V

Rated output power of the motor

240W-360W

Normal operating voltage range

85%-110%

5. Using RLXW20-11M micro switch, the continuous current that the contact can pass through is 10A at AC220V and 5A at DC220V.

6. Use the F10 type auxiliary switch. Normally, it is 10 open and 10 closed, and it can reach up to 24 open and 24 closed. The continuous current that can be passed through the contact is 10A at AC220V and 5A at DC220V.

7. The secondary connector is an imported industrial connector, the protection level of the outdoor mechanism can reach IP68 level, a mechanism is conventionally equipped with a 46-core industrial connector, and can also be equipped with two or three industrial connectors, and the secondary industrial connector has 24 pins, 32 pins, 46 pins and so on.

 
Diagram

Engineering Drawings
Ordering instructions
1. Control voltage and motor voltage;
2. an output angle;
3. Installation size;
4. Outdoor or indoor use;
5. The output mode of the output shaft; 6. The starting position (angle) of the output shaft when the opening position is opened; 7. The logarithm of the auxiliary contact of the auxiliary switch;