PRODUCT CENTER Three Position Mechanism
HYT5C型电动弹簧操动机构
HYT5C type Electric Spring Operating Mechanism
HYT5C electric spring operating mechanism is used for the opening and closing of fast grounding switch or fast disconnector or disconnecting switch, grounding switch and load switch with the required torque equivalent. The mechanism is designed as a splint structure, which is beautiful and reliable.
This mechanism uses the principle of spring symmetry and centering, and through the forward and reverse rotation function of the motor, the mechanism can compress the spring to achieve rapid opening and closing. The mechanism has two operation functions at the same time: manual and electric.
Technical Parameters

1. The output angle of this mechanism is 57+2 (can be customized according to user requirements, but the angle cannot exceed 90 degrees).

2. The spring output closing (opening) brake power is 260J.

3. Rated voltage energy storage time<6s.

4. Technical parameters of energy storage motor

    Model

HDZ-24503C type

Rated operating voltage

≈220V

Rated output power of the motor

450W

Normal operating voltage range

85%-110%

5. Use CSK type magnetic blow switch. The current that can be continuously passed through the contact is 10 at AC220V and 3A at ADC 220V.

6. Use the F10 type auxiliary switch. Normally, it is 10 open and 10 closed, and it can reach up to 20 open and 20 closed. The continuous current that can be passed through the contact is 10A at AC220V and 5A at DC220V.

7. The secondary connector is an imported industrial connector, and the protection level of the outdoor mechanism can reach IP68 level, and a mechanism can also be equipped with two or three industrial connectors with a 46-core industrial connector. There are several types of secondary industrial connectors, such as 24-pin, 32-pin, and 46-pin.

 
Diagram

Engineering Drawings

Ordering instructions
1. Control voltage and motor voltage;
2. an output angle;
3. Installation size;
4. Outdoor or indoor use;
5. The output mode of the output shaft; 6. The starting position (angle) of the output shaft when the opening position is opened; 7. The logarithm of the auxiliary contact of the auxiliary switch;