PRODUCT CENTER Three Position Mechanism
HYT5型 电动弹簧操动机构
HYT5 Electric Spring Operating Mechanism
The HYT5 spring operating mechanism can be used for the opening and closing of ZF port-126, ZF port-252 and the fast isolation switch and fast grounding switch with the required torque. This mechanism uses the principle of spring symmetry and centering, and through the forward and reverse rotation function of the motor, the mechanism can compress the spring to achieve rapid opening and closing. The mechanism adopts welded frame type, which is simple and stable in structure, and the layout can be changed according to the needs of users
The mechanism has two operation functions at the same time: manual and electric.
Technical Parameters

1. The output angle of this mechanism is 73+2% (can be customized according to user requirements, but the angle cannot exceed 90 degrees).

2. The spring output closing (opening) gate power is 169~244J.

3. The combined time of the institution < 6s

4. Technical parameters of energy storage motor

    Model

HDZ-23603C type

Rated operating voltage

≈220V

Rated output power of the motor

360W

Normal operating voltage range

85%-110%

5. Use CSK type magnetic blow switch. The current that can be continuously passed through the contact is 10A at AC220V and 3A at DC220V.

6. Use the F10 type auxiliary switch. Normally, it is 10 open and 10 closed, and it can reach up to 24 open and 24 closed. The continuous current that can be passed through the contact is 10A at AC220V and 5A at DC220V.

7. The secondary connector is an imported industrial connector, and the protection level of the outdoor mechanism can reach 1P68 level, and a mechanism is conventionally equipped with a 46-core industrial connector, and can also be equipped with two or three industrial connectors. The secondary industrial coupling is available in 24-pin, 32-pin, 46-pin and other models.

 
Diagram

Engineering Drawings

Ordering instructions
1. Control voltage and motor voltage;
2. an output angle;
3. Installation size;
4. Outdoor or indoor use;
5. The output mode of the output shaft; 6. The starting position (angle) of the output shaft when the opening position is opened; 7. The logarithm of the auxiliary contact of the auxiliary switch;